Water-Cooled Compressors

SHI’s Closed-loop Helium Compressors deliver high pressure, oil-free helium to both small and large-scale applications.

All SHI Cryocoolers, Pulse Tubes and Cryopumps are driven by highly-efficient and reliable helium compressors. These compressors boast industry-leading 20,000 or 30,000 hour maintenance intervals, and are available in single-phase and three-phase, low and high voltage, and water and air-cooled versions.

CSW-61 Indoor Water-Cooled Compressor Series

Specifications

Specifications
  CSW-61C CSW-61D
Electrical Supply 3 Phase
200-230 V, 50/60 Hz
3 Phase
378-528 V, 50/60 Hz
Power Consumption1 0.9 kW/pump (KZ-8L)
1.5 kW/pump (KZ-12L)
Ambient Temperature2 5-35 ºC (41-95 °F)
Cooling water (Inlet) 4-10 L/min. (1.1-2.6 gal./min.)
4-28 °C (40-82 °F)
Dimensions (HxWxD) 865 x 455 x 660 mm
(34.1 x 17.9 x 26.0 in.)
865 x 455 x 640 mm
(34.1 x 17.9 x 25.2 in.)
Weight 130 kg (287 lbs.)
Maintenance 30,000 Hours
  • 1.Typical power consumption
  • 2.Cooling capacity may degrade if ambient temperature is above 28 °C (82 °F).

Specifications subject to change without notice.

HC-4E Indoor Water-Cooled Compressor Series

Specifications

Specifications
Electrical Supply1 1 Phase
200 V, 230/240 V, 50 Hz
208/230 V, 60 Hz
Power Consumption2 2.6 kW at 50 Hz
3.0 kW at 60 Hz
Ambient Temperature3 4-40 ºC (40-104 °F)
Cooling water (Inlet) 2.7 L/min. (0.7 gal./min.)
4-27 °C (40-80 °F)
Dimensions (HxWxD) 504 x 430 x 485 mm
(19.8 x 16.9 x 19.1 in.)
Weight 75 kg (165 lbs.)
85 kg (180 lbs.) w/transformer
Maintenance 30,000 Hours
  • 1.Power may differ depending upon the cold head used.
  • 2.Typical power consumption
  • 3.Cooling capacity may degrade if ambient temperature is above 28 °C (82 °F).

Specifications subject to change without notice.

CKW-21A Indoor Water-Cooled Compressor Series

Specifications

Specifications
Electrical Supply1 3 Phase
200 V, 50/60 Hz
Power Consumption2 2.7-3.3 kW at 50 Hz
3.5-4.0 kW at 60 Hz
Ambient Temperature3 5-35 ºC (41-95 °F)
Cooling water (Inlet) 3.0-3.5 L/min. (0.8-0.9 gal./min.)
28 °C (82 °F)
Dimensions (HxWxD) 471 x 401 x 450 mm
(18.5 x 15.8 x 17.7 in.)
Weight 70 kg (155 lbs.)
Maintenance 20,000 Hours
  • 1.Power may differ depending upon the cold head used.
  • 2.Typical power consumption
  • 3.Cooling capacity may degrade if ambient temperature is above 28 °C (82 °F).

Specifications subject to change without notice.

HC-8E Indoor Water-Cooled Compressor Series

Specifications

Specifications
Electrical Supply1 3 Phase
220 V, 50 Hz
220/230 V, 60 Hz
Power Consumption2 3.7 kW at 50 Hz
4.3 kW at 60 Hz
Ambient Temperature3 4-40 ºC (40-104 °F)
Cooling water (Inlet) 5.7-9.5 L/min. (1.5-2.5 gal./min.)
4-21 °C (40-70 °F)
Dimensions (HxWxD) 504 x 430 x 485 mm
(19.8 x 16.9 x 19.1 in.)
Weight 75 kg (165 lbs.)
Maintenance 30,000 Hours
  • 1.Power may differ depending upon the cold head used.
  • 2.Typical power consumption
  • 3.Cooling capacity may degrade if ambient temperature is above 28 °C (82 °F).

Specifications subject to change without notice.

F-50 Indoor Water-Cooled Compressor Series

Specifications

Specifications
  F-50L F-50H
Electrical Supply1 3 Phase
200 V,
50/60 Hz
3 Phase
380, 400, 415 V, 50 Hz
480 V, 60 Hz
Power Consumption2 6.5-7.2 kW at 50 Hz
7.5-8.3 kW at 60 Hz
Ambient Temperature3 5-35 ºC (41-95 °F)
Cooling water (Inlet) 7-10 L/min. (1.8-2.6 gal./min.)
28 °C (82 °F)
Dimensions (HxWxD) 591 x 450 x 588 mm
(23.3 x 17.7 x 23.2 in.)
Weight 120 kg (264 lbs.)
Maintenance 30,000 Hours
  • 1.Power may differ depending upon the cold head used.
  • 2.Typical power consumption
  • 3.Cooling capacity may degrade if ambient temperature is above 28 °C (82 °F).

Specifications subject to change without notice.

F-100 Indoor Water-Cooled Compressor Series

Specifications

Specifications
  F-100L F-100H
Electrical Supply1 3 Phase
200 V, 50 Hz
200, 230 V, 60 Hz
3 Phase
380, 400, 415 V, 50 Hz
460, 480 V, 60 Hz
Power Consumption2 11.8-13.7 kW at 50 Hz
14.5-16.3 kW at 60 Hz
Ambient Temperature3 5-35 ºC (41-95 °F)
Cooling water (Inlet) 6-10 L/min. (1.6-2.6 gal./min.)
4-28 °C (39-82 °F)
Dimensions (HxWxD) 1331 x 511 x 512 mm
(52.4 x 20.1 x 20.2 in.)
Weight 250 kg (551 lbs.)
Maintenance 30,000 Hours
  • 1.Typical power consumption
  • 2.Cooling capacity may degrade if ambient temperature is above 28 °C (82 °F).

Specifications subject to change without notice.

F-70 Indoor Water-Cooled Compressor Series

Specifications

Specifications
  F-70L F-70H
Electrical Supply1 3 Phase
200 V,
50/60 Hz
3 Phase
380-415 V, 50 Hz
480 V, 60 Hz
Power Consumption2 6.6-6.9 kW at 50 Hz
7.5-7.8 kW at 60 Hz
Ambient Temperature3 4-40 ºC (40-104 °F)
Cooling water (Inlet) 6-9 L/min. (1.6-2.4 gal./min.)
5-25 °C (41-77 °F)
Dimensions (HxWxD) 532 x 443 x 493 mm
(20.9 x 17.4 x 19.4 in.)
Weight 100 kg (225 lbs.)
Maintenance 30,000 Hours
  • 1.Power may differ depending upon the cold head used.
  • 2.Typical power consumption
  • 3.Cooling capacity may degrade if ambient temperature is above 28 °C (82 °F).

Specifications subject to change without notice.