Water-Cooled Compressors
SHI’s Closed-loop Helium Compressors deliver high pressure, oil-free helium to both small and large-scale applications.
All SHI Cryocoolers, Pulse Tubes and Cryopumps are driven by highly-efficient and reliable helium compressors. These compressors boast industry-leading 20,000 or 30,000 hour maintenance intervals, and are available in single-phase and three-phase, low and high voltage, and water and air-cooled versions.
CNA-11 Indoor Air-Cooled Compressor Series
Specifications
Specifications
|
CNA-11B |
CNA-11C |
Electrical Supply1 |
1 Phase 100 V 50/60 Hz |
1 Phase 100, 120, 220, 230, 240 V, 50/60 Hz |
Power Consumption2 |
1.2-1.3 kW at 50 Hz 1.3-1.5 kW at 60 Hz |
Ambient Temperature3 |
4-38 ºC (39-100 °F) |
Cooling Air |
2.7 m3/min. (95 cfm), 50 Hz 3.3 m3/min. (117 cfm), 60 Hz |
Dimensions (HxWxD) |
400 x 390 x 450 mm (15.7 x 15.3 x 17.7 in.) |
610 x 390 x 450 mm (24.0 x 15.4 x 17.7 in.) |
Weight |
42 kg (73 lbs.) |
75 kg (165 lbs.) |
Maintenance |
30,000 Hours |
- 1.Power may differ depending upon the cold head used.
- 2.Typical power consumption
- 3.Cooling capacity may degrade if ambient temperature is above 28 °C (82 °F).
Specifications subject to change without notice.
Zephyr® Indoor Air-Cooled Compressor Series
Specifications
Specifications
Electrical Supply1 |
1 Phase 200 V, 220 V, 230/240 V, 50 Hz 220 V, 60 Hz |
Power Consumption2 |
3.0 kW at 50 Hz 3.4 kW at 60 Hz |
Ambient Temperature3 |
4-32 ºC (40-90 °F) |
Cooling Air |
20 m3/min. (706 cfm), 50/60 Hz |
Dimensions (HxWxD) |
715 x 453 x 488 mm (28.2 x 17.8 x 19.2 in.) |
Weight |
102 kg (225 lbs.) 111 kg (245 lbs.) w/transformer |
Maintenance |
30,000 Hours |
- 1.Power may differ depending upon the cold head used.
- 2.Typical power consumption
- 3.Cooling capacity may degrade if ambient temperature is above 28 °C (82 °F).
Specifications subject to change without notice.
FA-40 Indoor Air-Cooled Compressor Series
Specifications
Specifications
|
FA-40L |
FA-40H |
Electrical Supply1 |
3 Phase 200 V, 50/60 Hz |
3 Phase 380-415 V, 50 Hz 460-480 V, 60 Hz |
Power Consumption2 |
3.6-3.8 kW at 50 Hz 4.6-4.8 kW at 60 Hz |
Ambient Temperature3 |
4-38 ºC (40-100 °F) |
Cooling Air |
22 m3/min. (777 cfm), 60 Hz |
Dimensions (HxWxD) |
889 x 442 x 493 mm (35.0 x 17.4 x 19.4 in.) |
Weight |
110 kg (242 lbs.) |
Maintenance |
30,000 Hours |
- 1.Power may differ depending upon the cold head used.
- 2.Typical power consumption
- 3.Cooling capacity may degrade if ambient temperature is above 28 °C (82 °F).
Specifications subject to change without notice.
CSA-71A Indoor Air-Cooled Compressor Series
Specifications
Specifications
Electrical Supply1 |
3 Phase 200 V, 50/60 Hz |
Power Consumption2 |
6.5-7.2 kW at 50 Hz 7.5-8.3 kW at 60 Hz |
Ambient Temperature3 |
5-35 ºC (41-95 °F) |
Cooling Air |
28 m3/min. (989 cfm), 50/60 Hz |
Dimensions (HxWxD) |
885 x 550 x 550 mm (34.8 x 21.7 x 21.7 in.) |
Weight |
140 kg (309 lbs.) |
Maintenance |
20,000 Hours |
- 1.Power may differ depending upon the cold head used.
- 2.Typical power consumption
- 3.Cooling capacity may degrade if ambient temperature is above 28 °C (82 °F).
Specifications subject to change without notice.
CNA-61 Indoor/Outdoor Air-Cooled Compressor Series
Specifications
Specifications
|
CNA-61C |
CNA-61D |
Electrical Supply1 |
3 Phase 200 V, 50/60 Hz |
3 Phase 380, 400, 415 V, 50 Hz 460, 480 V, 60 Hz |
Power Consumption2 |
7.5-8.0 kW at 50 Hz 8.5-9.2 kW at 60 Hz |
Ambient Temperature3 |
5-35 ºC (41-95 °F) - Indoor Unit -30-45 ºC (-22-133 °F) - Outdoor Unit |
Cooling Air |
29.7 m3/min. (1049 cfm), 50 Hz 29.8 m3/min. (1052 cfm), 60 Hz |
Dimensions (HxWxD) |
630 x 270 x 570 mm (24.8 x 10.6 x 22.4 in.) |
705 x 270 x 610 mm (27.8 x 10.6 x 24.0 in.) |
Weight (Indoor/Outdoor Units) |
45 kg (95 lbs.)/ 115 kg (254 lbs.) |
55 kg (121 lbs.)/ 115 kg (254 lbs.) |
Maintenance |
20,000 Hours |
- 1.Power may differ depending upon the cold head used.
- 2.Typical power consumption
- 3.Cooling capacity may degrade if ambient temperature is above 28 °C (82 °F).
Specifications subject to change without notice.
FA-70 Indoor/Outdoor Air-Cooled Compressor Series
Specifications
Specifications
|
FA-70L |
FA-70H |
Electrical Supply1 |
3 Phase 200 V, 50/60 Hz |
3 Phase 380/400/415 V, 50 Hz 460-480 V, 60 Hz |
Power Consumption2 |
6.9-7.2 kW at 50 Hz 7.9-8.2 kW at 60 Hz |
Ambient Temperature3 |
4-40 ºC (39-104 °F) - Indoor -30-45 ºC (-22-113 °F) - Outdoor |
Cooling Air |
22 m3/min. (777 cfm), 60 Hz |
Dimensions (HxWxD) |
547 x 262 x 637 mm (21.5 x 10.3 x 25.1 in.) - Indoor 948 x 1016 x 391 mm (37.3 x 40.0 x 15.4 in.) - Outdoor |
Weight (Indoor/Outdoor Units) |
46 kg (101 lbs.)/ 142 kg (313 lbs.) |
Maintenance |
30,000 Hours |
- 1.Power may differ depending upon the cold head used.
- 2.Typical power consumption
- 3.Cooling capacity may degrade if ambient temperature is above 28 °C (82 °F).